Schneider LC1D Series Contactor (9A-95A) AC24V/36V/48V/110V/220V/380V
شحن مجاني عند طلبك أكثر من 200 درهم إماراتي
Couldn't load pickup availability
Schneider TeSys LC1D Series AC Contactor 9A–95A
Schneider Electric TeSys LC1D series AC contactors cover 9A, 12A, 18A, 25A, 32A, 40A, 50A, 65A, 80A and 95A (AC-3). They are 3-pole electromagnetic contactors used to start/stop three-phase motors, pumps, fans, compressors, HVAC units, lighting and resistive loads. Coil options include AC24V, AC110V, AC220V and AC380V; mounting is standard 35 mm DIN rail or screw-fixed panel. For motor duty, pair an LC1D contactor with an LRD thermal overload relay.
Key Features
- Series: Schneider TeSys D / Deca (LC1Dxx)
- Poles: 3P (main contacts 3NO); built-in 1NO + 1NC auxiliary
- Current range: 9A – 95A AC-3
- Rated voltage: power circuit up to 690V AC
- Coil voltage: AC24V / AC36V / AC48V / AC110V / AC220V / AC380V (DC coil available on specific models)
- Utilisation: AC-3 (motor), AC-1 (resistive), AC-4 (heavy starting)
- Mounting: 35 mm DIN rail / panel screw
- Standards: IEC 60947-4-1, EN 60947-4-1; CE/CCC/UL/CSA on genuine Schneider models
- Terminals: screw clamp (L1/T1, L2/T2, L3/T3; coil A1/A2)
- Typical life: millions of mechanical operations on TeSys D frames
LC1D 9A–95A Selection Table (400V AC-3)
| Model | AC-3 Current | Motor Power @400V | Typical Use |
|---|---|---|---|
| LC1D09 | 9A | 4 kW | Small pumps, fans, 3-phase 5HP@480V |
| LC1D12 | 12A | 5.5 kW | Conveyors, small compressors |
| LC1D18 | 18A | 7.5 kW | Machine tools, blowers |
| LC1D25 | 25A | 11 kW | Water pumps, mixers |
| LC1D32 | 32A | 15 kW | Industrial fans, feeders |
| LC1D40 | 40A | 18.5 kW | Compressors, crushers |
| LC1D50 | 50A | 22 kW | Large pumps, HVAC plant |
| LC1D65 | 65A | 30 kW | Process machines |
| LC1D80 | 80A | 37 kW | Heavy conveyors, mills |
| LC1D95 | 95A | 45 kW | Big motors, star-delta starters |
Rule: Pick LC1D frame whose AC-3 current ≥ motor full-load current. For high ambient temperature, frequent starts, or AC-4 duty, go one frame size up.
Coil Code Reference
- LC1D09M7 = 9A contactor, AC220V coil
- LC1D25F7 = 25A contactor, AC110V coil
- LC1D95Q7 = 95A contactor, AC380V coil
- BD suffix = DC24V coil (e.g. LC1D09BD)
Common Accessories
- Overload relay: TeSys LRD / LR2 → motor overload protection
- Auxiliary block: LA7D / LADN → extra NO/NC contacts
- Circuit breaker: Miniature circuit breaker (MCB) or motor protection circuit breaker upstream
- Surge / Snubber: For inductive coil switching in PLC panels
FAQ
Is LC1D09 the same as CJX2 / TeSys D style?
Can I use a 9A contactor for a 7.5kW motor?
Coil voltage vs motor voltage — what matters?
Do LC1D contactors need an overload relay?
3-pole or 4-pole?
Field Experience Note
In field panels we usually size the contactor from the motor nameplate FLA, not from kW alone. A 4kW motor at 400V is about 8.5A, so LC1D09 is okay; a 5.5kW motor is about 11A, so LC1D12; an 11kW motor is about 22A, so LC1D25. If the panel runs in a hot enclosure or the motor starts 20+ times per hour, move up one frame. Always mount the LRD overload directly under the contactor and feed the coil from a clean control supply.