CHINT ELECTRIC
CHINT V9 Under Voltage Release for NB1, NBH8, NB1L,NBH8LE
شحن مجاني عند طلبك أكثر من 200 درهم إماراتي
Couldn't load pickup availability
SPECIFICATIONS
CHINT V9 Under Voltage Release for NB1, NBH8, NB1L,NBH8LE
Brand Name: CHNT
Type: Mini
Origin: Mainland China
Is Smart Device: no
Certification: NONE
Model Number: for NB1
1. Major function
To be assembled with circuit breaker to achieve over/under voltage protection
2. Parameters and performance
Rated operation voltage Ue: AC 240V, 50Hz;
Overvoltage operation setting value Uvo: 280V;
Rated insulation voltage Ui: 500V; Tripping characteristics: the release is assembled with NB1-63 series circuit breaker. When the applied voltage is reduced to 35%Ue or increased to 95% ~ 105% of the over-voltage setting value, the release should drive the circuit breaker to act. When the applied voltage is below 35%Ue or above 105% of the over-voltage setting value, the release should be able to prevent the circuit breaker from closing. When the supply voltage is above 85% Ue and below 95% of over-voltage setting value, the circuit breaker should be able to close normally. The upper limit of the applied voltage should be less than 110% over-voltage operation setting value. Mechanical and electrical life: the mechanical and electrical life after the release is assembled with the circuit breaker should be ??? 4000 cycles, of which, 500 cycles for over-voltage trip
3. Assembly and installation of the product
OUVT-X1 can be assembled with NB1-63 series circuit breaker, with the assembly diagram shown below: