CHINT NXC + NXR Starter Kit

CHINT NXC + NXR Starter Kit Pairing Table (400V 3φ, DOL, AC-3)

Basis: 3-phase 400V, cosφ≈0.85, η≈0.87. Contactor sized to AC-3 Ie ≥ FLC×1.25; NXR thermal setpoint = 0.95–1.05 × nameplate FLC. Always verify against the motor nameplate; upsize one frame for frequent starts (>30/hr) or high ambient (>40°C).

Motor kW

Motor HP*

Est. FLC @400V (A)

AC-3 Ie needed (A)

Recommended NXC

NXC AC-3 Ie (A)

Recommended NXR

NXR range (A)

NXR setpoint (A)

Upstream MCB (C, A)

Typical use

0.37

0.5

0.8

1.0

NXC-09

9

NXR-25

0.4–22

0.7–0.8

6

Small pump / fan

0.55

0.75

1.1

1.4

NXC-09

9

NXR-25

0.4–22

1.0–1.1

6

Small pump / fan

0.75

1.0

1.5

1.9

NXC-09

9

NXR-25

0.4–22

1.4–1.5

6

Small pump / fan

1.1

1.5

2.1

2.7

NXC-09

9

NXR-25

0.4–22

2.0–2.3

6

Conveyor / compressor

1.5

2.0

2.9

3.6

NXC-09

9

NXR-25

0.4–22

2.8–3.1

6

Conveyor / compressor

2.2

3.0

4.3

5.4

NXC-09

9

NXR-25

0.4–22

4.1–4.5

10

Workshop pump

3.0

4.0

5.8

7.3

NXC-09

9

NXR-25

0.4–22

5.6–6.1

10

Workshop pump

4.0

5.4

7.8

9.7

NXC-12

12

NXR-25

0.4–22

7.4–8.2

16

Machine tool / cooler

5.5

7.4

10.7

13.4

NXC-18

18

NXR-25

0.4–22

10.2–11.3

20

Compressor

7.5

10.1

14.6

18.3

NXC-25

25

NXR-25

0.4–22

13.9–15.4

25

Large pump / fan

11

14.7

21.4

26.8

NXC-32

32

NXR-25

0.4–22

20.4–22.5

32

Industrial pump

15

20.1

29.2

36.5

NXC-38

38

NXR-38

15–34

27.8–30.7

40

Large fan / compressor

18.5

24.8

36.0

45.0

NXC-50

50

NXR-100

30–90

34.3–37.9

50

Air compressor

22

29.5

42.9

53.6

NXC-65

65

NXR-100

30–90

40.8–45.1

63

Heavy conveyor

30

40.2

58.4

73.0

NXC-80

80

NXR-100

30–90

55.6–61.5

80

Large pump group

37

49.6

72.0

90.0

NXC-95

95

NXR-100

30–90

68.6–75.8

100

Mixer / agitator

45

60.3

87.6

109.5

NXC-95+

95

NXR-100

30–90

83.4–92.2

125

Big pump / stirrer

 

Typical Starter Kit bundles

  • ≤4 kW small motors: NXC-09 + NXR-25 + 6–10A C-curve MCB → pumps, fans, small conveyors

  • 5.5–11 kW common range: NXC-18 / NXC-25 / NXC-32 + NXR-25 → compressors, machine-tool coolers

  • 15–22 kW mid range: NXC-38 / NXC-50 + NXR-38 / NXR-100 → large fans, air compressors

  • 30–45 kW heavy duty: NXC-80 / NXC-95 + NXR-100 → large pump groups, agitators

Shop links

  • CHINT NXC contactors (NXC-09/12/18/25/32, AC 24–380V coil): https://www.electric-b2c.com/products/original-chint-nxc-09-nxc-12-nxc-18-nxc-25-nxc-32-lc1-nxc-contactor-magneti

  • CHINT Kunlun NXR thermal overload relays (0.4–100A, NXR-25/38/100): https://www.electric-b2c.com/products/chnt-kunlun-nxr-25-nxr-38-nxr-100-thermal-overload-relay-0-4-100a

⚠️ Notes: *HP = kW×1.34 (approx.); size from kW/FLC, not HP. NXR-25 max setting ~22A, so 11kW still fits; 15kW+ moves to NXR-38/NXR-100. NXR side-couples to NXC via bracket — no extra wiring for the trip contact. For >45kW consider NXC-115/150, soft starter or VFD, and verify IEC Type 2 coordination.

العودة إلى المدونة

اترك تعليقًا

يرجى ملاحظة أنه يجب الموافقة على التعليقات قبل نشرها.